Mitsubishi Electric FR-E700 Instruction Manual page 80

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Connection of stand-alone option units
Connection example with the FR-BR(-H) type resistor
3-phase AC
power supply
Fig. 3-38: Connection with the brake unit FR-BU2
If the control contacts are only specified for 230 V control power you must install a transformer
when using a 400 V power supply.
Normal: across TH1-TH2 ... close, Alarm: across TH1-TH2 ... open
Connect the inverter terminals (P/+, N/ ) and brake unit terminals so that their terminal signals
match with each other. (Incorrect connection will damage the inverter.)
A jumper is connected across BUE and SD in the initial status.
The wiring distance between the inverter, brake unit and resistor unit should be within 5m. If
twisted wires are used, the distance should be within 10 m.
CAUTION:
E
● If the transistors in the brake unit should become faulty, the resistor can be unusually hot,
causing a fire. Therefore, install a magnetic contactor on the inverters input side to configure
a circuit so that a current is shut off in case of fault.
● Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
3 - 44
T
Inverter
Motor
M
3~
5 m
Wiring
ON
OFF
002045E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720s sc ecFr-e720s sc eneFr-e740 sc ecFr-e740 sc ene

Table of Contents