Parameter
Parameter reading
The following program reads Pr. 7 "Acceleration time" of station 1 inverter to D1.
● Pr. 7 "Acceleration time" reading instruction code: H07 (hexadecimal)
● For information about the instruction codes refer to the parameter list on page A-16.
● The reply code at the time of instruction code execution is set to D2.
(For information about the reply code (RWr2) refer to page 6-360.)
SM1536
SD1536.0
SD1540.0
(0)
M0
X20
(4)
M300
(8)
M301
X100F
(10)
M302
X100F
(17)
(25)
Fig. 6-181: Program example 5
NOTE
For parameters having numbers 100 and later, change their link parameter extended settings (set
them to other than H00). Refer to page A-16 for details.
FR-E700 SC EC/ENE
M0
Check the data link status of the station 1
PLS
M300
SET
M301
Write Pr. 7 read code (H07) to RWw2.
MOV
H7
W102
Turn on the instruction code execution request
SET
Y100F
(RY0F)
RST
M301
SET
M302
Read acceleration time (RWr3) and reply code
MOV
W3
D1
(RWr2) to D1 and D2 when the instruction code
execution completion (RX0F) turns on.
MOV
W2
D2
Turn off the instruction code execution request
RST
Y100F
(RY0F)
RST
M302
END
CC-Link IE Field Network Basic
I003134E
6 - 369