1.3

CC-Link IE TSN communication specifications

The communication specification varies depending on the specification of the master.
Item
Transmission speed
Minimum synchronization cycle
CC-Link IE TSN authentication class
Communication method
Synchronization function
Maximum number of connected units
Maximum distance between nodes
Maximum number of branches
Topology
Connection cable
Connector
Node type
RX
RY
Maximum cyclic size
(of one node)
RWr
RWw
12
PRE-OPERATION INSTRUCTIONS
1 Gbps/100 Mbps
125.00 μs
B
Time sharing method
Compliant with IEEE 802.1AS and IEEE 1588v2
121 units (sum of master and slave stations)
100 m
No upper limit within the same Ethernet system
Line, star, ring, or a combination of line and star
Ethernet cable
(IEEE 802.3 1000BASE-T compliant cable or ANSI/TIA/EIA-568-B (Category 5e) compliant
shielded 4-pair branched cable)
Shielded RJ-45
Slave station
64 bits
64 bits
128 words
128 words
Description