Mitsubishi Electric FR-E700 Instruction Manual page 535

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Troubleshooting
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
FR-E700 SC EC/ENE
PS
PU Stop
Stop with the STOP/RESET key of the PU is set in Pr. 75 "Reset selection/disconnected PU detec-
tion/PU stop selection". (For Pr. 75, refer to section 6.17.1.)
Check for a stop made by pressing the STOP/RESET key of the operation panel.
Turn the start signal off and release with PU/EXT key.
RB
Regenerative brake prealarm
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 "Special regenerative
brake duty" value. When the setting of Pr. 70 "Special regenerative brake duty" is the initial value
(Pr. 70 = 0), this warning does not occur.
If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV ) occurs.
The RBP signal can be simultaneously output with the [RB] display. For the terminal used for the
RBP signal output, assign the function by setting "7 (positive logic) or 107 (negative logic)" in any
of Pr. 190 to Pr. 192 "Output terminal function selection". (Refer to section 6.10.5.)
Check that the brake resistor duty is not high.
Check that the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative brake
duty" values are correct.
Increase the deceleration time (Pr. 8).
Check the Pr. 30 "Regenerative function selection" and Pr. 70 "Special regenerative brake
duty" values.
TH
Electronic thermal relay function prealarm
Appears if the cumulative value of the Pr. 9 "Electronic thermal O/L relay" reaches or exceeds 85%
of the preset level. If it reaches 100% of the Pr. 9 "Electronic thermal O/L relay" setting, a motor
overload trip (E. THM) occurs. The THP signal can be simultaneously output with the [TH] display.
For the terminal used for THP signal output, assign the function by setting "8 (positive logic) or
108 (negative logic)" in any of Pr. 190 to Pr. 192 "Output terminal function selection"). (Refer to
section 6.10.5.)
1)Check for large load or sudden acceleration.
2) Is the Pr. 9 "Electronic thermal O/L relay" setting is appropriate? (Refer to section 6.8.1.)
1) Reduce the load weight or the number of operation times.
2) Set an appropriate value in Pr. 9 "Electronic thermal O/L relay". (Refer to section 6.8.1.)
MT
Maintenance signal output
Indicates that the cumulative energization time of the inverter has reached a given time.
When the setting of Pr. 504 "Maintenance timer alarm output" set time is the initial value (Pr. 504
= 9999), this warning does not occur.
The Pr. 503 "Maintenance timer" setting is larger than the Pr. 504 "Maintenance timer alarm out-
put set time" setting. (Refer to section 6.21.3.)
Setting "0" in Pr. 503 "Maintenance timer" erases the signal.
Causes and corrective actions
FR-PU04
PS
FR-PU07
FR-PU04
RB
FR-PU07
FR-PU04
TH
FR-PU07
FR-PU04
FR-PU07
7 - 7