Parameter
● Error response
An error response is returned if the query message received from the master has an illegal
function, address or data. No response is returned for a parity, CRC, overrun, framing or busy error.
NOTE
No response message is sent in the case of broadcast communication also.
Error response (Response message)
Slave Address
Message
Slave address
Function
Exception code
Tab. 6-97: Description of response data
Code
01
02
03
Tab. 6-98: Error code list
An error will not occur in the following cases:
– Function code H03 (Read Holding Register Data )
When the No. of Points is 1 or more and there is one or more holding registers from which data
can be read.
– Function code H10 (Write Multiple Holding Register Data)
When the No. of Points is 1 or more and there is 1 or more holding registers to which data can
be written.
Namely, when the function code H03 or H10 is used to access multiple holding registers, an error
will not occur if a non-existing holding register or read disabled or write disabled holding register
is accessed.
NOTES
An error will occur if all accessed holding registers do not exist.
Data read from a non-existing holding register is 0, and data written there is invalid.
FR-E700 SC EC/ENE
Function
H80 + Function
(8 bits)
(8 bits)
Error Item
Description
ILLEGAL FUNCTION
The set function code in the query message from the master cannot be handled
(Function code illegal)
by the slave.
The set register address in the query message from the master cannot be han-
ILLEGAL DATA ADDRESS
dled by the inverter.
(Address illegal)
(No parameter, parameter read disabled, parameter write disabled)
The set data in the query message from the master cannot be handled by the
ILLEGAL DATA VALUE
inverter.
(Data illegal)
(Out of parameter write range, mode specified, other error)
Exception Code
(8 bits)
Description
Set the address received from the master.
The master-requested function code + H80 is set.
The code in the following table is set.
Communication operation and setting
CRC Check
L
(8 bits)
H
(8 bits)
6 - 275