Selection and protection of a motor
6.8.3
To exhibit the best performance of the motor performance
(offline auto tuning) (Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859)
The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
● When performing advanced magnetic flux vector control or general-purpose magnetic flux vector
control, the motor can be run with the optimum operating characteristics by automatically
measuring the motor constants (offline autotuning) even when each motor constants differs,
other manufacturer's motor is used, or the wiring length is long.
Pr. No. Name
71
Applied motor
80
Motor capacity
81
Number of motor poles
82
Motor excitation current
83
Rated motor voltage
84
Rated motor frequency
90
Motor constant (R1)
91
Motor constant (R2)
92
Motor constant (L1)
93
Motor constant (L2)
94
Motor constant (X)
96
Auto tuning setting/status
859
Torque current
The above parameters can be set when Pr. 160 "User group read selection" = 0.
6 - 90
Initial Value
Setting Range
0/1–3–6/13–16/
0
23/24/40/43/44/
50/53/54
0.1–15 kW
9999
9999
2/4/6/8/10
9999
9999
0–500 A
9999
9999
200 V class
200 V
0–1000 V
400 V class
400 V
50 Hz
10–120 Hz
9999
0–50 /9999
9999
0–50 /9999
9999
0–1000 mH/9999
9999
0–1000 mH/9999
9999
0–100%/9999
0
1
0
11
21
0–500 A
9999
9999
Description
By selecting a standard motor or constant-
torque motor, thermal characteristic and
motor constants of each motor are set.
Applied motor capacity.
V/F control
Number of motor poles.
V/F control
Tuning data
(The value measured by offline auto tuning
is automatically set.)
Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants.
Rated motor voltage (V).
Rated motor frequency (Hz).
Tuning data
(The value measured by offline auto tuning
is automatically set.)
9999: Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants.
Offline auto tuning is not performed
For advanced magnetic flux vector control
Offline auto tuning is performed without
motor running (all motor constants).
For general-purpose magnetic flux vector
control
Offline auto tuning is performed without
motor running.
(motor constant (R1) only)
Offline auto tuning for V/F control
(automatic restart after instantaneous
power failure (with frequency search))
Tuning data
(The value measured by offline auto tuning
is automatically set.)
Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants.
Parameter
Refer to
Parameters referred to
Section
7
Acceleration time
6.7.1
8
Deceleration time
6.7.1
9
Electronic thermal O/L
6.8.1
relay
71
Applied motor
6.8.2
80
Motor capacity
6.2.1
81
Number of motor
6.2.1
poles
156
Stall prevention
6.3.5
operation selection
178–184
Input terminal
6.10.1
function selection
190–192
Output terminal
6.10.5
function selection
800
Control method
6.2.1
selection

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-e720s sc ecFr-e720s sc eneFr-e740 sc ecFr-e740 sc ene

Table of Contents