Reference Of The Terminal Am (Analog Voltage Output) (Pr. 55, Pr. 56) - Mitsubishi Electric FR-E700 Instruction Manual

Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Monitor display and monitor output signals
6.11.3

Reference of the terminal AM (analog voltage output) (Pr. 55, Pr. 56)

Analog voltage output from the terminal AM is available. Set the reference of the signal output from
terminal AM.
Pr. No. Name
Frequency monitoring
55
reference
Current monitoring
56
reference
The above parameters can be set when Pr. 160 "User group read selection" = 0.
The above parameter allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
Frequency monitoring reference (Pr. 55)
Set the full scale value when outputting the frequency monitor from terminal AM. Set the frequency
to be referenced when the frequency monitor (output frequency/set frequency) is selected for the
terminal AM display.
● Set the frequency (output frequency/set frequency) when the voltage output at terminal AM is
10 V DC. The analog voltage output and frequency at terminal AM are proportional. (The maxi-
mum output voltage is 10 V DC.).
10 V DC
6 - 148
Initial Value
Setting Range
50 Hz
0–400 Hz
Rated inverter
0–500 A
current
Initial value
Setting range of Pr. 55
Description
Full-scale value to output the output
frequency monitor value to terminal AM.
Full-scale value to output the output current
monitor value to terminal AM.
Fig. 6-73:
Frequency monitoring reference
Parameter
Refer to
Parameters referred to
Section
158 AM terminal function
6.11.2
selection
I001164E