Input/Output Phase Failure Protection Selection (Pr. 251, Pr. 872); Overspeed Detection (Pr. 374); Encoder Signal Loss Detection (Pr. 376) - Mitsubishi Electric FR-A700 Instruction Manual

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

4.18.3 Input/output phase failure protection selection (Pr. 251, Pr. 872)

You can disable the output phase failure protection function that stops the inverter output if one of the inverter
output side (load side) three phases (U, V, W) opens.
The input phase failure protection function of the inverter input side (R/L1, S/L2, T/L3) can be made valid.
Parameter
Name
Number
Output phase failure protection
251
selection
Input phase failure protection
872
selection
(1) Output phase failure protection selection (Pr. 251)
When Pr. 251 is set to "0", output phase failure protection (E.LF) becomes invalid.
(2) Input phase failure protection selection (Pr. 872)
⋅ When Pr. 872 is set to "1", input phase failure protection (E.ILF) is provided if a phase failure of one phase among
the three phases is detected for 1s continuously.
REMARKS
If an input phase failure has occurred when Pr. 872 = "1" (input phase failure protected) and a value other than "0" (power failure
stop function valid) is set in Pr. 261, input phase failure protection (E.ILF) is not provided but power-failure deceleration is made.
CAUTION
⋅ When an input phase failure occurs in the R/L1 and S/L2 phases, input phase failure protection is not provided but the
inverter output is shut off.
⋅ If an input phase failure continues for a long time, the converter section and capacitor lives of the inverter will be shorter.
♦ Parameters referred to ♦
Pr. 261 Power failure stop selection

4.18.4 Overspeed detection (Pr. 374)

Parameter
Name
Number
374
Overspeed detection level
Motor speed *
Pr. 374
ALM

4.18.5 Encoder signal loss detection (Pr. 376)

When the encoder signal is lost during encoder feedback control, orientation control, or vector control, signal loss
detection (E.ECT) is activated to stop the inverter output.
Parameter
Name
Number
Encoder signal loss
376
detection enable/disable
selection
* Setting can be made only when the FR-A7AP is mounted.
Initial Value
1
0
Refer to page 265
Initial Value
Setting Range
140Hz
Coast to stop
Time
* The output frequency and Pr. 374 are compared during
ON
real sensorless vector control.
E.OS
Initial Value
Setting Range
0
Operation setting at alarm occurrence
Setting Range
0
Without output phase failure protection
1
With output phase failure protection
0
Without input phase failure protection
1
With input phase failure protection
When the motor speed reaches or exceeds
the speed set in Pr. 374 during encoder
0 to 400Hz
feedback control, real sensorless vector
control, or vector control, over speed (E.OS)
occurs and stops the inverter output.
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Vector
Vector
Vector
Signal loss detection is invalid
0
1
Signal loss detection is valid
Description
Description
Description
271
4