6.16 Solid fuel boiler

6.16.1

General

The basic unit permits straightforward dT control of an uncontrolled solid fuel boiler with
boiler sensor, boiler pump and a selectable comparative temperature (DHW storage
tank, buffer storage tank, flow temperature setpoint, minimum setpoint).
The following functions are available:
dT controller with selectable comparative temperature
Minimum setpoint
Locking another heat source
Excess heat discharge
Boiler pump overrun
DHW charging priority
Hours run counter
Status display (operating state)
When configuring the solid fuel boiler diagram, sensor B22 and
solid fuel boiler pump Q10 must be parameterized at the
multifunctional inputs/outputs (BX, QX).
For the solid fuel boiler diagram to be activated and the
associated parameters to be displayed, the boiler sensor must
B22
T
be connected.
Q10
7471d37/1009