Acceptance Tests - Basic Functions; Safe Torque Off (Basic Functions) - Siemens SINAMICS G130 Manual

Safety integrated
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

10.5.1
Acceptance tests – Basic Functions
10.5.1.1

Safe Torque Off (Basic Functions)

Table 10- 8
"Safe Torque Off" function
No.
Note:
The acceptance test must be individually conducted for each configured control.
The control can be realized via terminals and/or via PROFIsafe.
1.
Initial state
Drive in "Ready" state (p0010 = 0)
STO function enabled (on-board terminals / PROFIsafe p9601.0 = 1 and/or p9601.3 = 1)
No Safety faults and alarms (r0945[0...7], r2122[0...7]); see note "non-critical alarms" in
section Acceptance tests.
r9772.17 = r9872.17 = 0 (STO deselection via terminals - DI CU / EP terminal Motor
Module); only relevant for STO via terminal
r9772.20 = r9872.20 = 0 (STO deselection via PROFIsafe); only relevant for STO via
PROFIsafe
r9772.0 = r9772.1 = 0 (STO deselected and inactive – Control Unit)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – Motor Module)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
r9774.0 = r9774.1 = 0 (STO deselected and inactive - group); only relevant for grouping
2.
Run the drive
Ensure that the correct drive is running
Select STO when you issue the traversing command and check the following:
The drive coasts to a standstill or is braked and stopped by the mechanical brake (if
available and configured (p1215, p9602, p9802)).
No Safety faults and alarms (r0945[0...7], r2122[0...7])
r9772.17 = r9872.17 = 1 (STO selection via terminal - DI CU / EP terminal Motor Module);
only relevant for STO via terminal
r9772.20 = r9872.20 = 1 (STO selection via PROFIsafe); only relevant for STO via
PROFIsafe
r9772.0 = r9772.1 = 1 (STO selected and active – Control Unit)
r9872.0 = r9872.1 = 1 (STO selected and active – Motor Module)
r9773.0 = r9773.1 = 1 (STO selected and active – drive)
r9774.0 = r9774.1 = 1 (STO selected and active - group); only relevant for grouping
3.
Deselect STO and check the following:
No Safety faults and alarms (r0945[0...7], r2122[0...7])
r9772.17 = r9872.17 = 0 (STO deselection via terminals - DI CU / EP terminal Motor
Module); only relevant for STO via terminal
r9772.20 = r9872.20 = 0 (STO deselection via PROFIsafe); only relevant for STO via
PROFIsafe
Safety Integrated
Function Manual, 05/2010, A5E03264275A
Description
Acceptance test and acceptance report
10.5 Acceptance tests
Status
265