7.3 Control of "STO" and "SS1" via terminals on the Control Unit and the Motor/Power Module
Terminal strip –X132 on the CU320-2 control unit
Table 7- 20
Terminal strip –X132 on the CU320-2 control unit
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section: 1.5 mm
DI: Digital input; DI/DO: Bidirectional digital input/output; M: Electronics ground; M2: Ground reference
1)
The rapid inputs can be used as probe inputs or as inputs for the external zero mark
2)
Data for: V
= 24 V; load 48 Ω; high ("1") = 90% V
3)
cc
Safety Integrated
Function Manual, 05/2010, A5E03264275A
Designation
1)
DI 4
DI 5
DI 6
DI 7
DI 20
DI 21
M2
M
DI/DO 12
DI/DO 13
M
DI/DO 14
DI/DO 15
M
2
; low ("0") = 10% V
out
Controlling the safety functions
Technical data
Voltage: -30 ... +30 VDC
Typical power consumption: 9 mA at 24 V
Electrical isolation: reference potential is M2 terminal
Level (incl. ripple)
High level: 15 ... 30 V
Low level: -30 ... +5 V
Input delay (typ.):
For "0" → "1": 50 μs
For "1" → "0": 150 μs
Reference potential for terminal 1 ... 6
Ground
As input:
Voltage: -30 ... +30 VDC
Typical power consumption: 9 mA at 24 V
Level (incl. ripple)
High level: 15 ... 30 V
Low level: -30 ... +5 V
DI/DO 12, 13, 14, and 15 are "rapid inputs"
Input delay (typ.):
For "0" → "1": 5 μs
For "1" → "0": 50 μs
As output:
Voltage: 24 V DC
Max. load current per output: 500 mA
Continued-short-circuit-proof
Output delay (typ./max.)
3)
For "0" → "1": 150 μs / 400 μs
For "1" → "0": 75 μs / 100 μs
Switching frequency:
For resistive load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: Max. 10 Hz
Maximum lamp load: 5 W