Safety Integrated Extended Functions
6.5 Safe Stop 2 (SS2)
Note
Activating SS2 may cause the device (PLC, motion controller) that governs the speed
setpoint to interrupt the ramp function (by triggering OFF2).
The device behaves in this way as a result of a fault reaction triggered by OFF3 activation.
This fault reaction can be avoided by assigning appropriate parameters or appropriate
wiring.
Responses
Speed limit violated (SBR):
● STOP A
● Safety message C01706/C30706
Standstill tolerance violated in p9330/p9530 (SOS):
● STOP B with subsequent STOP A
● Safety message C01707/C30707
System errors:
● STOP F with subsequent STOP A
● Safety message C01711/C30711
Overview of important parameters
● p1135[0...n] OFF3 ramp-down time
● p9301 SI Motion enable safety functions (Motor Module)
● p9501 SI Motion enable safety functions (Control Unit)
● p9330 SI Motion standstill tolerance (Motor Module)
● p9530 SI Motion standstill tolerance (Control Unit)
● p9348 SI Motion SBR actual velocity tolerance (Motor Module)
● p9548 SI Motion SBR actual velocity tolerance (Control Unit)
● p9352 SI Motion transition time STOP C to SOS (Motor Module)
● p9552 SI Motion transition time STOP C to SOS (Control Unit)
● r9722.0...15 CO/BO: SI Motion drive-integrated status signals
88
Safety Integrated
Function Manual, 05/2010, A5E03264275A