Standard Commissioning Of Safety Integrated Functions - Siemens SINAMICS G130 Manual

Safety integrated
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Commissioning
8.3 Commissioning of Safety Integrated functions
4. Click "Gear factor" and set the actual value tolerance (p9542) to a larger value (e.g. 10
5. Open SS1 and set the shutdown speed to >0.
6. Call the Safely-Limited Speed, change all of the stop responses to "[0]STOP A" or
7. The user-specific Safety settings can now be performed.
8. Click on "Copy parameters".
9. Switch off/switch on the drive to accept the changes.
Note
If, during acceleration or deceleration, the drive outputs the message C01711/C30711
(message value 1041 to1043), this indicates problems due to ramping that is too steep in
conjunction with the precontrol. You have the following options to remedy this:
• Reduce the ramp gradient.
• Use the extended ramp-function generator (with rounding) to set a more gentle ramp
• Reduce the precontrol.
• Change the values of parameters p9588 and p9589 (see specifications in the List
8.3.4

Standard commissioning of Safety Integrated functions

Standard commissioning of the safety functions
1. A commissioned project that has been uploaded to STARTER can be transferred to
2. If the source and target devices have different software versions, the reference
3. Once the project has been downloaded to the target device, an acceptance must be
192
mm/min or 10 rpm) and the number of motor revolutions to match the pole pair number
(r0313).
"[1]STOP B" and close the window.
up.
Manual).
another drive unit keeping the existing Safety parameter assignment.
checksums may have to be adapted. This is displayed via a fault:
Target checksum fault
p9729[0...2] - F01680(0...2)
p9399[0...1] - F30680(0...1)
p9799 - F01650 (fault value: 1000)
p9899 - F30650 (fault value: 1000)
p10005[0...1] - F01650(0...1) (TM54F)
carried out. This is indicated by fault F01650 (fault value: 2004 or 2005). For more
information on the acceptance test see chapter "Acceptance test and acceptance report".
Safety Integrated
Function Manual, 05/2010, A5E03264275A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120 chassisSinamics s120 cabinet modulesSinamics s150

Table of Contents