PROFIsafe status word (ZSW)
S_ZSW1, PZD1 in telegram 30, input signals
See function diagram [2840].
Table 7- 25
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12 ...
14
15
Safety Integrated
Function Manual, 05/2010, A5E03264275A
Description of the PROFIsafe status word (ZSW)
Meaning
STO active
SS1 active
SS2 active
SOS active
SLS active
Reserved
Reserved
Internal event
Reserved
Active SLS level bit 0
Active SLS level bit 1
SOS selected
Reserved
SSM (speed)
7.5 Control by way of PROFIsafe
1
STO active
0
STO not active
1
SS1 active
0
SS1 not active
1
SS2 active
0
SS2 not active
1
SOS active
0
SOS not active
1
SLS active
0
SLS not active
-
-
-
-
1
Internal event
0
No internal event
-
-
-
-
-
Display of the speed limit for SLS (2 bits)
-
1
SOS selected
0
SOS deactivated
-
-
1
SSM (speed below limit value)
0
SSM (speed higher than/equal to limit)
Controlling the safety functions