11.6
Start the universal controller
Configure a start condition for the universal controller.
The controller is stopped and started via a digital signal.
"Current setpoint" is displayed with "---" when a universal controller is stopped.
The controller always runs without configured start condition.
Main menu > Commissioning > Extra configuration > Controller 1...3 >
Operating line
Start condition
11.7
Assign texts
Adapt the texts for the universal controller via operation.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Controller 1...3 >
Operating line
Controller x
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
Switching and monitoring device RMS705B
Universal controller
Adjustable values / Comment
---, N.X1, N.X2, ...
(digital values only).
Starts the controller, all outputs to 0%.
Range
Max. 20 characters
Factory setting
Controller x