Function Check / Wiring Test - Siemens Synco 700 RMZ785 Basic Documentation

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Setting values
Display values
Wiring test
Siemens
Building Technologies
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Faults > Fault relay 1...2 >
Operating line
Fault priority
Indication of fault
Inversion
* Factory setting for "Fault relay 2": "Fault via bus (audibly)".
** Max. 1 bus fault message can be processed (even if the priorities are different). Recommendation: Do
not configure 2 bus fault relays.
At menu item "Aggregates", the state of the 2 fault relays can be read.
Main menu > Aggregates > Faults >
Operating line
Fault relay 1
Fault relay 2
12.6

Function check / wiring test

During the wiring test, the two fault relays can be enabled directly:
Main menu > Commissioning > Wiring test > Outputs >
Operating line
Fault relay 1
Fault relay 2
Switching and monitoring device RMS705B
Faults
Range
Urgent, Not urgent, All
Fault internally (optically), Fault
internally (audibly), Fault via bus
(audibly) **
Yes, No
Current state
Off, On
Off, On
Comment
Off, On
Off, On
Factory setting
All
Fault internally
(audibly) *
No
181 / 216
CE1P3124en
01.04.2010