11.3

Universal shift

11.3.1 Enable universal shift
Assign an input to enable this function.
Main menu > Commissioning > Extra configuration > Controller 1...3 >
Operating line
Universal shift
11.3.2 Mode of operation
The setpoint can be shifted from a universal input or an internal analog signal.
 Refrigeration: Shifting the flow temperature setpoint for the chilled ceiling by
room enthalpy or the surface temperature.
 Ventilation: Shifting by room humidity or surface temperature.
 General: Shifting by outside temperature.
Setpoint shifting acts on "Setpoint high/low" and "Eco setpoint high/low" as per the
following diagram:
E
1
Switching and monitoring device RMS705B
Universal controller
Adjustable values / Comment
---, N.X1, N.X2, ..., internal analog
(analog values only).
Key:
2
E
2
Xn
F
2
E
2
F
1
E
1
1
SpH
SpL
SpHEco
SpLEco
Xn
W
Xn
[Setp compensation 2]
delta
end
[Setp compensation 2]
start
[Setp compensation 2]
[Setp compensation 1]
start
end
[Setp compensation 1]
delta
[Setp compensation 1]
Setpoint high
Setpoint low
high
Eco setpoint
Eco setpoint
low
Input variable:
Current setpoint
CE1P3124en
01.04.2010