Siemens Synco 700 RMZ785 Basic Documentation page 185

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Example 1
Data exchange concept
Configuration
Device 1
Device 2
Configuration diagram
186 / 216
Siemens
Building Technologies
The air quality average value of 2 air quality sensors is available in RMS705B
(device 1). This value is sent as transmission object via an analog output and
handled by RMS705B (device 2).
The following transmission and reception zone is engineered for the example:
RMS705B, device 1
Terminal
Transmission
zone
N.Y1
1
= Transmission
= Reception
Configure the following in RMS705B, device 1:
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
N.Y1
Configure the following in RMS705B, device 2:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
N.X1
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
N.X1
X
N.Y1
Switching and monitoring device RMS705B
Communication
RMS705B, device 2
Terminal
Reception zone
N.X1
1
Range
1
Range
ppm
Range
1
KNX
Unit 1
zone 1
Value
Air quality average
Factory setting
Factory setting
Factory setting
Unit 2
CE1P3124en
01.04.2010