8.3.11 Start condition 1, 2, 3, 4
The start condition inputs are required to:
 Define the load from several signals to start several aggregates.
 Generate an analog load signal from several signals.
The start conditions are not evaluated until the precommand input is On if a
precommand input is configured and the precommand input state is Off.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1...2 >
Operating line
Start condition 1
Start condition 2
Start condition 3
Start condition 4
You can set "[switching value n] On" and "[switching value n] Off" for inputs "Start
condition 1..4" to create a digital signal from a modulating signal.
Enter the value in percent that is to be effective during switch-on of the
corresponding start condition via "[switching n] load".
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
[Switching value 1] on
[Switching value 1] off
[Switching value 1] load
[Switching value 2] on
[Switching value 2] off
[Switching value 2] load
[Switching value 3] on
[Switching value 3] off
[Switching value 3] load
[Switching value 4] on
[Switching value 4] off
[Switching value 4] load
8.3.12 Fault message for aggregates (A...D)
You can configure a fault message for aggregates A...D if you want the aggregate
to switch off in a controlled manner in the event of a fault. Changeover selects the
next available aggregate in the linear rotary step switch.
Switching and monitoring device RMS705B
Aggregates
Adjustable values / Comment
---, X1, X2, ...
---, X1, X2, ...
---, X1, X2, ...
---, X1, X2, ...
Range
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Factory setting
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
CE1P3124en
01.04.2010