Note
Configuration
Setting values
104 / 216
Siemens
Building Technologies
8.3.11 Start condition 1, 2, 3, 4
The start condition inputs are required to:
Define the load from several signals to start several aggregates.
Generate an analog load signal from several signals.
The start conditions are not evaluated until the precommand input is On if a
precommand input is configured and the precommand input state is Off.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1...2 >
Operating line
Start condition 1
Start condition 2
Start condition 3
Start condition 4
You can set "[switching value n] On" and "[switching value n] Off" for inputs "Start
condition 1..4" to create a digital signal from a modulating signal.
Enter the value in percent that is to be effective during switch-on of the
corresponding start condition via "[switching n] load".
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
[Switching value 1] on
[Switching value 1] off
[Switching value 1] load
[Switching value 2] on
[Switching value 2] off
[Switching value 2] load
[Switching value 3] on
[Switching value 3] off
[Switching value 3] load
[Switching value 4] on
[Switching value 4] off
[Switching value 4] load
8.3.12 Fault message for aggregates (A...D)
You can configure a fault message for aggregates A...D if you want the aggregate
to switch off in a controlled manner in the event of a fault. Changeover selects the
next available aggregate in the linear rotary step switch.
Switching and monitoring device RMS705B
Aggregates
Adjustable values / Comment
---, X1, X2, ...
---, X1, X2, ...
---, X1, X2, ...
---, X1, X2, ...
Range
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Depending on selected type
Depending on selected type
0...100 %
Factory setting
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
Type-dependent
Type-dependent
25 %
CE1P3124en
01.04.2010