8.4.11 Motor fault
Output motor fault is "On" in the case of a fault when the motor no longer is able
to transport the medium. It is used to forward the fault information to another
aggregate.
The following table shows the output motor fault state for the corresponding
causes of fault:
Motor type
1, 2-speed motor
or twin motor
1 or 2-speed motor
1 or 2-speed motor
Twin motor
Twin motor
Twin motor
Twin motor
Twin motor
Switch off another aggregate with motor fault.
DI
V
V
DO
8.4.12 Start and stop conditions
You can configure two inputs as start and stop conditions for each motor block.
Main menu > Commissioning > Extra configuration > Aggregates > Motor > Motor 1...6 >
Operating line
Start condition 1
Start condition 2
Stop condition 1
Stop condition 2
Stop conditions take priority over start conditions (see Section 8.4.19).
The speed start condition determines which speed is to be enabled during switch-
on by start condition 1 or 2 at the motor.
Switching and monitoring device RMS705B
Aggregates
Fault
[Mot 1] precom no checkb signal
[Motor 1] no flow
[Motor 1] overload
[Motor 1] fault
[Motor 1A] no flow
[Motor 1B] no flow
[Motor 1A] overload
[Motor 1A] overload
N.Q1
Adjustable values / Comment
---, N.X1, N.X2,... (digital and analog inputs).
---, N.X1, N.X2,... (digital and analog inputs).
---, N.X1, N.X2,... (digital and analog inputs).
---, N.X1, N.X2,... (digital and analog inputs).
"Motor fault " state
On
On
On
On
Off
Off
Off
Off
C
Logic 1
N.Q3
N.Q2
CE1P3124en