Siemens Synco 700 RMZ785 Basic Documentation page 122

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Wiring test
Note
Setting values
Display values
Setting values
Note
Siemens
Building Technologies
8.4.16 Wiring test
During the wiring test, the motors can be directly switched via the control switch.
Main menu > Commissioning > Wiring test > Outputs >
Operating line
Comment
Motor 1...
Off, Speed 1, Speed 2
Motor 6
(2-speed motor on display).
[Motor 1] A...
Off, On
[Motor 6] A
(1-speed motor, twin motor on display).
[Motor 1] B...
Off, On
[Motor 6] B
(twin motor on display).
Adjustable times acting directly on the relay are effective (run-up time, coasting
time).
8.4.17 Assign texts
Adapt the texts for the motors via operation. They are displayed at the relevant
operating line and on the menu.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Motor 1...
Max. 20 characters
Motor 6
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
8.4.18 Operating hours
The total number of operating hours is acquired for each motor output. The counter
counts to max. 99 999 hours and then rolls over to 0.
Main menu > Aggregates > Motor > Motor 1...6 >
Operating hours motor A
Operating hours motor B
You can adapt the counter value at the password level, and e.g. reset it to 0.
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Operating hours motor A
Operating hours motor B
The operating hours for speeds 1 and 2 are summarized for the 2-speed motor
(sum of 1 and 2).
Switching and monitoring device RMS705B
Aggregates
0...99'999 h
0...99'999 h
Range
0...99'999 h
0...99'999 h
Factory setting
Motor 1...
Motor 6
Factory setting
0
0
123 / 216
CE1P3124en
01.04.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Synco 700 rmz788Synco 700 rms705bSynco 700 rmz787

Table of Contents