Siemens Synco 700 RMZ785 Basic Documentation page 78

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Example
Configuration
Configuration
Siemens
Building Technologies
8.3.1
Activate block
Activate the rotary step switch by assigning command
Do this via the motor block to be connected, the logic block or the continuous
output, i.e. from their configuration menus.
See the following example:
Command
of output A is to act on Logic block 1.
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Operating line
[Logic A] input 1
Note the following for output switching:
 Configure the outputs without gap (order A,B,C,D).
 Assign the smallest load to command A in the event of different loads.
 Use the type ("Linear", "Flexible", "Binary") to set the step switch properties.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1...2 >
Operating line
Type
Switching and monitoring device RMS705B
Aggregates
Setting (example)
[Rot step swi 1A] command
Range
Linear, Flexible, Binary
or load
to output A.
Factory setting
Linear
79 / 216
CE1P3124en
01.04.2010