Example
Changeover period
Setting values
Note
Settings
Siemens
Building Technologies
Control of a twin pump by the motor block.
You can enter a changeover period for orderly changeover of run priority.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Changeover period
 If a negative number is entered, both motors are switched on for the period of
time set during changeover.
 If a positive number is entered, the second motor can switch on only after the
time has expired after the first motor has switched off.
The changeover period is also considered for the motor kick.
You can set a run-up time for the twin motor. The motor operating state is indicated
after the run-up time expires.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Runup time
Switching and monitoring device RMS705B
Aggregates
Range
 60...60 s
Range
00.00... 59.59 m.s
X
Factory setting
0 s
Factory setting
00.10 m.s
111 / 216