Signal Converter; Min-Max-Average - Siemens Synco 700 RMZ785 Basic Documentation

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Purpose
Note
Configuration
Inputs split
Siemens
Building Technologies
9

Signal converter

9.1

Min-max-average

"Min-Max-Average" executes the following calculations from the signals from inputs
1 to 5:
 Selection of minimum input signal (Min).
 Selection of maximum input signal (Max).
 Calculation of average value (Avr).
2 "Min-Max-Average" blocks are available:
The calculated values are provided as DC 0...10 V signals (Y) and internal, analog
signals (a).
The calculations do not consider non-configured inputs.
9.1.1
Enable Min-Max-Average
Assign an input to enable this function.
Main menu > Commissioning > Extra configuration > Signal converter > Min-Max-Average
1...2
Operating line
Input 1
Input 2
Input 3
Input 4
Input 5
Inputs split
Min-Max-Average A
Function output A
Min-Max-Average B
Function output B
 The calculations are carried out separately for the function ranges A and B if
parameter "Inputs split" is enabled (Yes).
Function range A: Inputs 1 and 2.
Function range B: Inputs 3 to 5.
 The calculations are carried out on all configured inputs if "Inputs split" is
disabled (factor setting No).
Switching and monitoring device RMS705B
Signal converter
Adjustable values / Comment
---, N.X1, N.X2, ...
---, N.X1, N.X2, ...
---, N.X1, N.X2, ...
---, N.X1, N.X2, ...
---, N.X1, N.X2, ...
Yes, No
---, N.Y1, N.Y2, ... /
enable modulating output.
Minimum, Maximum, Average
---, N.Y1, N.Y2, ... /
enable modulating output.
Minimum, Maximum, Average
Factory setting
No
Minimum
Minimum
127 / 216
CE1P3124en
01.04.2010