C Demand, H/C Changeover; Heat Demand Function - Siemens Synco 700 RMZ785 Basic Documentation

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Purpose
Enabling
Purpose
Configuration
Siemens
Building Technologies
10
H/C demand, H/C changeover
10.1

Heat demand function

10.1.1 Purpose and enabling
The "Heat demand" function acquires heat demand from a heat distribution zone
via the bus. The collected heat requests can be routed to another zone or further
handled as a resulting setpoint condition (temperature request signal, heating flow
setpoint) as a continuous or digital signal.
Contrl.
To enable function "Heat demand", assign the load signal of a controller, enable the
primary controller or assign output Q, d, Y, a.
10.1.2 Use universal controller as consumer
Use "Extra configuration > Aggregates > Heat demand" at the corresponding
controller for a sequence of the controller to generate heat demand (see Section
10.3 for application examples).
X
Contrl.
Main menu > Commissioning > Extra configuration > Aggregates > Heat demand >
Operating line
Controller 1
Controller 2
Controller 3
This allows for generating a "Heat demand" signal that can be used by another
device on the KNX.
To do this, set a heat distribution zone.
Main menu > Commissioning > Communication > Distribution zones >
Operating line
Heat distribution zone
Switching and monitoring device RMS705B
H/C demand, H/C changeover
Adjustable values / Comment
---, Sequence 1
---, Sequence 1
---, Sequence 1
Range
1...31
Factory setting
1
137 / 216
CE1P3124en
01.04.2010