Acknowledge and reset
Example
Note
Functions
Note
194 / 216
Siemens
Building Technologies
Applies to all fault messages that must be acknowledged and reset on RMS705B.
After acknowledgement on RMS705B, the fault message is maintained until the
fault is no longer present. Only then can the fault message on RMS705B be reset.
After resetting, the LED in the fault button extinguishes.
A pump with fault contact is connected to the motor block's overload message. The
fault contact of the pump is reset if the pump switches off because of this fault
message.
Manually acknowledge and reset the fault on RMS705B to restart the pump.
RMS705B does not allow for acknowledging fault messages from other Synco
devices.
14.2.3 Delete fault messages
The operator unit allows for deleting the "Fault history" list at the service level via
operating line "Delete faults".
Main menu > Faults >
Operating line
Delete faults
When enabling this function, all other fault messages are reset. Only pending faults
continue to be displayed.
You may not be able to acknowledge or reset the fault message if the type of
acknowledgement is changed at a pending fault.
You can also use the "Delete faults" function to reset these fault messages!
Switching and monitoring device RMS705B
Support for errors and faults
Comment
All current faults are reset internally, the "Fault history"
list is deleted.