8.4.14 Motor kick
To prevent the motors (pumps) from seizing during longer off periods (e.g. heating
group in summer), a periodic motor kick can be enabled for each motor block.
 When motor kick is active, the motors are switched on for 30 seconds once a
week regardless of any other functions and settings.
 The motor kick is enabled by setting "Motor kick" to "Yes". If the setting is "No",
there is no motor kick.
 In addition, a "Kick day" and "Kick time" can be set.
 With the motor kick, the precommand output with its settable times is enabled
prior to the actual motor start. All other delay times are inactive.
 The first speed is switched on for 2-speed motor operation, and both motors are
switched on alternating for twin motor operation.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Motor kick
Kick day
Kick time
8.4.15 Display values
The current state of the motors is displayed on the operator unit.
Main menu > Aggregates > Motor > Motor 1...6 >
Operating line
[Motor 1]
precommand...
[Motor 6] precommand
Motor 1...6
Main menu > Aggregates > Motor > Motor 1...6 >
Operating line
[Motor 1]
precommand...
[Motor 6] precommand
[Motor 1] A...
[Motor 6] A
[Motor 1] B...
[Motor 6] B
Switching and monitoring device RMS705B
Aggregates
Range
Yes, No
Mo, Tu, We, Th, Fr, Sa, Su
00:00...23:59 h. m
Comment
Off, On.
Display of current motor speed:
Off, On or Off, Speed 1, Speed 2
Comment
Off, On.
Display of current motor speed:
Off, On.
Display of current motor speed:
Off, On.
Factory setting
No
Mo
10:00 h.m
CE1P3124en
01.04.2010