Function "Multiple use of sensors" allows for wiring a passive signal at an input
terminal directly to a Y-output and provide it as a DC 0...10 V signal. The signal
can then be fed to other devices.
Ally passive temperature signal types (LG-Ni1000, 2x LG-Ni1000, T1, Pt1000) can
be converted and used multiple times.
Main menu > Commissioning > Extra configuration > Sensor multiple use >
Operating line
Signal Y N.X1... Signal
Y RMZ787 (2).X4
When converting a passive signal to an DC 0...10 V signal, the preset allocation of
passive signal and temperature range can be adapted as needed. Do this via
parameters "Value low" and "Value high" (see Section 5.2.2).
5.3

Digital inputs

Control function signals can be connected to the digital inputs.
Activate the digital inputs as described in Section 5.1.
5.3.1
Normal position
You can define the "Normal" position for each digital input.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line
Normal position
Switching and monitoring device RMS705B
Inputs
Adjustable values / Comment
N1.Y1...A8(2).Y2 /
Activate function by assigning an input terminal to the
output terminal.
Range
Open, Closed
Factory setting
Open
35 / 216