Start conditions with switching
command outputs
(Example 2.2)
Configuration
Siemens
Building Technologies
Load input,
Number of
start condition
stages or
aggregates
A+B+C+D
Description:
- 4 evaporator pumps available for 3 single-stage refrigeration machines.
- Max. 3 pumps are operating at the same time (1 standby).
- An evaporator pump is switched on each time a refrigeration machine is released.
- The run priority of the pumps changes periodically between the 4 pumps (first in, first Out). - The next
pump is switched on in the event of a fault (fault changeover).
- The function diagram shows a snapshot: Sequence ABC in operation; A takes priority; D in standby.