Siemens Synco 700 RMZ785 Basic Documentation page 82

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Start conditions with switching
command outputs
(Example 2.2)
Configuration
Siemens
Building Technologies
Load input,
Number of
start condition
stages or
aggregates
A+B+C+D
Description:
- 4 evaporator pumps available for 3 single-stage refrigeration machines.
- Max. 3 pumps are operating at the same time (1 standby).
- An evaporator pump is switched on each time a refrigeration machine is released.
- The run priority of the pumps changes periodically between the 4 pumps (first in, first Out). - The next
pump is switched on in the event of a fault (fault changeover).
- The function diagram shows a snapshot: Sequence ABC in operation; A takes priority; D in standby.
Plant diagram
Evp
1
DI
AI
DO
AO
Configuration diagram *
*
The start conditions of the rotary step switch are configured as per the refrigeration machine
releases.
Main menu > Commissioning > Extra configuration > Aggregates > Rotary step switch >
Rotary step switch 1...2 >
Operating line
Type
Switching and monitoring device RMS705B
Aggregates
Output configuration
A
B
1
4
Start
x
d
d
T
3
2
1
1
2
2
3
3
4
4
4x
4x
Rotary
step switch 1
X
Setting
Linear
Run priority
C
D
changeover
d
d
Function diagram
C
B
A
100 %
0 %
X
P
C D
C
D
C
CE1P3124en
Yes
Q
D
83 / 216
01.04.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Synco 700 rmz788Synco 700 rms705bSynco 700 rmz787

Table of Contents