Basic configuration
Configuration
Function
Add further inputs and outputs with extension modules RMZ785, RMZ787, and RMZ788.
RMZ785
Controller functions are configured to these inputs/outputs.
RMZ787 (1), (2)
Specify which modules are connected to RMS705B in which order (position); max 4 modules.
RMZ788 (1), (2)
Input identifiers
Inputs
Configuration
(Section 5)
N.X1...RMZ788(2).X4
N.X1
x
Y
Outside temperature
N.X1
OT
[Controller 1] rem setp adj
N.X1
[Controller 2] rem setp adj
[Controller 3] rem setp adj
Pulse
N.X1
Siemens
Building Technologies
16.2.3 Overview of configuration diagrams
Functions
Enter input identifier
Units:
°C, %, g / kg, kJ / kg, W / m², m / s, bar, mbar, Pa, ppm, universal 000.0
(display with one decimal place), universal 0000 (display without decimal
place).
The unit is only required for presentation on the display. The unit presents
all unit-dependent settings (e.g. P-bands) on the unit.
Sensor for °C:
LG-Ni1000, 2xLG-Ni1000 (averaging), T1, Pt1000, DC 0...10 V, all other
units DC 0...10 V, adjustable range.
Digital (input for potential-free contacts).
Pulse (up to 25 Hz for mechanical source (Reed contact),
or up to 100 Hz for electronic source).
Special identifiers: Outside temperature, remote setpoint adjuster.
With the special identifiers, internal connections are taken directly from
RMS705B.
A name can be assigned to each input.
Outside temperature for the following functions:
Connect one outside temperature sensor.
The bus can be used to receive the outside temperature.
Sensor as listed above under "Sensor for °C.
Rem setp1: Absolute for controller 1 to 3
(0...1000 or DC 0...10 V).
Select input identifier "Pulse" for an input.
Connection of a pulse source (mechanical or electronic).
Pulse source type can be assigned to the input.
Switching and monitoring device RMS705B
Appendix