X1
X2
X3
Y1
Y2
Key
RMZ785
RMZ787
RMZ788
Key
Siemens
Building Technologies
15.2

Connection terminals

15.2.1 RMS705B
X4
X5
X6
Y3
Y4
G, G0
Rated voltage AC 24 V.
G1
Power supply AC 24 V for active sensors, detectors, monitors or signal
sources.
M
Measuring neutral for signal input.
G0
System neutral for signal output.
X1...X8
Universal signal inputs for LG-Ni1000, 2x LG-Ni1000 (averaging),
T1, Pt1000, DC 0...10 V, 0...1000  (setpoint), pulse,
contact query (potential-free).
Y1...Y4
Control or status outputs, analog DC 0...10 V.
Q2x/3x/6x/7x
Potential-free relay outputs (N.O. contact) for AC 24...230 V.
Q1x/Q4x
Potential-free relay outputs (changeover contact) for AC 24...230 V.
CE
KNX bus data line, positive.
CE
KNX bus data line, negative.
15.2.2 Universal modules RMZ785, RMZ787, RMZ788
X1
X2 M G1
X3 M
M
RMZ785
X1
X2
X3
RMZ787
X1
X2
X3
RMZ788
Y1
Y2
M
Measuring neutral for signal input.
G0
System neutral for signal output.
G1
Power supply AC 24 V for connected active devices.
X1...X8
Universal signal inputs for LG-Ni1000, 2x LG-Ni1000 (averaging),
T1, Pt1000, DC 0...10 V, 0...1000  (setpoint),
contact query (potential-free), pulse.
Y1, Y2
Control or status outputs, analog DC 0...10 V.
Q1x/2x/3x
Potential-free relay outputs (N.O. contact) for AC 24...230 V.
Q5x
Potential-free relay outputs (changeover contact) for AC 24...230 V.
Switching and monitoring device RMS705B
Electrical connections
X7
X8
Q11
Q23
Q12
Q14
Q24
X4 M G1
X5
M
X6 M G1
X4
Q13
Q23
Q14
Q24
X4
Q13
Q51
Q14
Q52
Q54
Q33
Q41
Q63
Q73
Q34
Q42
Q44
Q64
Q74
X7 M
X8 M
Q51
Q33
Q34
Q54
Q52