Siemens Synco 700 RMZ785 Basic Documentation page 112

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Run priority changeover
Setting value
Changeover by time
Changeover in case of
fault
Manual changeover
Setting values
Siemens
Building Technologies
Run priority changeover can be automatic, manual, or in the case of fault.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Run priority
Motor A
Motor B
Automatic
If the selection in operating line "Run priority" is "Automatic", the run priority
automatically changes weekly. Changeover occurs at the time set for motor kick.
Assign the run priority to a pump by selecting the required pump in operating line
"Run priority" if changeover by time is not what you want.
If a motor is faulty, the run priority is changed over to the other motor. After the fault
is acknowledged and reset, the same run priority as prior to the fault is resumed.
For testing, you can manually change over the run priority. To do this, select the
desired motor in operating line "Run priority". When returning the run priority to
"Automatic", the run priority remains active at the current motor until the next
changeover by time.
8.4.5
Delay times
You can set a "Switch-on delay", "Switch-off delay", "On time minimum" and "Off
time minimum" for motors.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Switch-on delay
Switch-off delay
On time minimum 1
On time minimum 2*
Off time minimum
* Adjustable only for 2-speed motors.
 "Switch-off delay" and "Off time minimum" always act during the switch-off
command for motors switched off via stop command or via removal of the start
condition.
 "Switch-on delay" and "On time minimum" always act during the switch-on
command for motors switched on via start condition.
 The above times are not effective during switch-off command by motor kick or
while a fault is present.
Switching and monitoring device RMS705B
Aggregates
Range
00.00...59.59 m.s
00.00...59.59 m.s
00.00...59.59 m.s
00.00...59.59 m.s
00.00...59.59 m.s
Factory setting
Automatic
Factory setting
00.00 m.s
00.00 m.s
00.00 m.s
00.00 m.s
00.00 m.s
113 / 216
CE1P3124en
01.04.2010