Input terminal simulation
Each input terminal can be simulated to test plant reaction.
Main menu > Inputs > Simulation inputs >
Operating line
N.X1...
A8 (2).X4
Only authorized staff may override inputs within a limited period of time!
During terminal simulation, fault message "Simulation inputs active" is triggered.
No.
Text
100
Simulation inputs active
This message remains active until "Simulation " returns to "----". This ensures that
a simulation is always reset on the plant.
The simulated outside temperature is used only locally; it is not sent via bus to
other controllers.
5.1.4
Troubleshooting
RMS705B among other issues checks if input terminal simulation is still active
when the Commissioning menu is exited.
No.
Text
101...
[N.X1] sensor error ...
264
RMZ788(2).X4 sensor error
5.1.5
Function check / wiring test
During the wiring test, the measured values of all inputs can be checked.
Main menu > Commissioning > Wiring test > Inputs >
Operating line
N.X1
...
RMZ788(2).X4
Switching and monitoring device RMS705B
Inputs
Range
(type-dependent)
----, 50... 50 °C
Effect
Non-urgent message; must not be
acknowledged.
Effect
Non-urgent message; must not be
acknowledged.
Adjustable values / Comment
Display of the current measured value.
ditto
ditto
Factory setting
(type-dependent)
----