2.2.4
Access level
An access right is defined for each parameter (operating line). There are 3 access
levels:
Access level
Access
User level
The user level is always accessible.
(for plant
Users can adjust visible, editable operating lines.
operators)
Service level
Press the OK knob and the ESC button at the
(for maintenance
same time, then select operating line "Service
tasks)
level" and confirm by pressing the OK knob.
Password level
Press the OK knob and the ESC button at the
(for
same time, select operating line "Password level"
commissioning)
and confirm by pressing the OK knob. Enter "7"
as password and confirm by pressing the OK
knob.
The access level determines which individual menus and operating lines are
activated. At a higher access level, all menus and operating lines of the lower
access levels are visible.
The levels use a common menu tree as a base (the password level shows the
entire menu tree).
Switch from the current access level to another access level:
1. Press both OK knob and ESC button simultaneously.
The "Access levels" menu is displayed.
2. Select the required access level by turning the OK knob and press to confirm.
3. Enter "7" to access the "Password level".
RMS705B times out after 30 minutes without user interaction and enters "User
level".