Modulating load input with
switching command and
modulating load outputs
(Example 3)
Configuration
Siemens
Building Technologies
Load input,
Number of
start condition
stages or
aggregates
A+B
a
Description:
- 2 refrigeration machines with different capacities have an internal output control (e.g. hot gas
bypass) controlled in sequence to a common flow temperature.
- Typical capacity profile: Aggregate A (min. output = 0.5 kW, rated output = 3 kW), Aggregate B (min.
output 1 kW; rated output 6 kW).
- The total output at X
= 100 % is 9 kW.
P
Plant diagram
1
1
DI
AI
DO
AO
Configuration diagram
Modul. output
Modul. output
A
B
Main menu > Extra configuration > Aggregates > Rotary step switch > Rotary step switch
1...2 >
Operating line
Type
Main menu > Commissioning > Settings >... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Output A
Min output A
Output B
Min output B
Switching and monitoring device RMS705B
Aggregates
Output configuration
A
B
1
4
Start
d
a
d
a
Function diagram (not to dimensions)
T
2
2
Rotary
step switch 1
X
Setting
Flexible
Range
0.1...999.9
0.0...999.9
0.1...999.9
0.0...999.9
Run priority
C
D
changeover
+
B
B
A
A
0 %
X
P
C D
C
D
Setting
3.0
0.5
6.0
1.0
CE1P3124en
No
100 %
Q
93 / 216