8.1.3
Setting values switching value On and Off
The logic can process digital and analog signals. Setting values "[Logic x switching
value n] on" and "[Logic x switching value n] off" are used to convert a continuous
signal to a 2-position signal (On/Off).
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line
[Logic A switching value 1] on
[Logic A switching value 1] off
[Logic A switching value 2] on
[Logic A switching value 2] off
[Logic A switching value 3] on
[Logic A switching value 3] off
[Logic B switching value 1] on
[Logic B switching value 1] off
[Logic B switching value 2] on
[Logic B switching value 2] off
8.1.4
Switch-on/switch-off delay
For the logic output, a switch-on and switch-off delay can be set.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line
Switch-on delay
Switch-off delay
* See Notes on the time format in Section 8.1.1
The switch-on delay always acts on the switch-on command; the switch-off delay
on the switch-off command.
8.1.5
Minimum on time
For the logic output, a min. switch-on time can be set. Thus, the output remains set
to On for the set time when a switch-on command is received.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line
On time minimum
* See Notes on the time format in Section 8.1.1
The minimum on-time always takes effect after a switch-on command.
Switching and monitoring device RMS705B
Aggregates
Range
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Depending on selected type
Range
00.00...59.59 m.s or*
00.00...23.50 h.m
00.00...59.59 m.s or*
00.00...23.50 h.m
Range
00.00...59.59 m.s or*
00.00...23.50 h.m
Factory setting
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Type-dependent
Factory setting
00.00 m.s
00.00 m.s
Factory setting
00.00 m.s
CE1P3124en
01.04.2010