5.4
Pulse
An input with this identifier can be used to connect a pulse counter. Pulses with the
following specification can be received:
Mechanical sources (Reed contact) without Namur circuitry, max. pulse
frequency of 25 Hz and a min. 20 ms pulse duration.
Electronic pulse source with max. pulse frequency of 100 Hz and min. 5 ms
pulse duration.
5.4.1
Activate function
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Adjustable values / Comment
...X...
Pulse
Electronic pulse sources (e.g. Open Collector outputs) generate shorter, less
bouncing pulses than mechanical pulse sources (e.g. relays or Reed contacts).
The type is adjustable.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Type
Mechanically or Electronically
5.4.2
Connection diagram
G
+/-
+/-
R1
G
X...
M
G0
G0
R1
Reed pulse source.
Switching and monitoring device RMS705B
Inputs
Factory setting
Mechanically