Siemens Synco 700 RMZ785 Basic Documentation page 57

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Setting
Free text
58 / 216
Siemens
Building Technologies
6.5.2
Limits for output and user-defined unit
The calculated output signal of the modulating output (Y) can be limited high and
low.
In addition, you can assign a user-defined unit.
The output result's unit (K, kW, etc.) is entered as characters and displayed
together with the output value.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Data acquisition > Calculator > Calculator 1...2 >
Operating line
Unit
Value low
Value high
Value low and Value high only limit the DC 0...10 V signal run to the Y-output.
10 V
0 %
0 V
Value low
6.5.3
Assign texts
A specific text can be assigned to each calculator.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Data acquisition > Calculator > Calculator 1...2 >
Operating line
Calculator 1...2
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
Switching and monitoring device RMS705B
Data acquisition
Range
Max. 20 characters
-50...9999
-50...9999
Value high
Range
Max. 20 characters
Factory setting
0
100
Factory setting
Calculator 1...2
CE1P3124en
01.04.2010