Display values
Note
Wiring test
Wrong formulas
Examples for wrong
formulas
Fault messages
Siemens
Building Technologies
6.5.4
Display values and wiring test
The following values are displayed on the operator unit:
Main menu > Data acquisition > Calculator 1...2 >
Operating line
Actual value
Unit
Input A
Input B
Input C
 Consider possible number ranges of the result when writing a formula. Change
to another unit (e.g. kJ rather than J) if you can expect the result to be large.
 Actual value Is an integer or floating point number depending on whether you
use integers (x, y, z) or floating point constants (u, v, w).
You can directly control the calculator during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Operating line
[Calculator 1] ouput
[Calculator 2] ouput
6.5.5
Troubleshooting
The result and thus the calculator output is set to 0 if an input signal required for
calculation is not available during operation.
User-defined formulas are checked for conformity to rules (see Section 6.5.1). A
configuration alarm is displayed when a formula contains errors.
Wrong formulas
AB*
A*/B
A*((B-C)
A*(((B-C)-x)-z)
No.
Text
6401
[Calculator 1] formula invalid
6402
[Calculator 2] formula invalid
Switching and monitoring device RMS705B
Data acquisition
Comment
–50... +9999 or –50.0... +999.9
Max. 20 characters
Comment
---, 0...100 %
---, 0...100 %
Error description
2 variables without operator.
2 operators.
Final parenthesis missing.
Max. 2 same parentheses in sequence.
Effect
Non-urgent message; must not be
acknowledged.
Non-urgent message; must not be
acknowledged.