Siemens Synco 700 RMZ785 Basic Documentation page 98

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Example
Setting values
Run-up delay
Locking time
Restart time
Siemens
Building Technologies
8.3.5
Command ( )
An aggregate is controlled via command output A...D ( ).
Normally, the command output sends the signal via the motor block to output
terminal Q(x).
Rotary
step switch 1
X
N.Q1
N.Q2
You can set for all steps a common "Runup delay", "Locking time", and "Restart
time" for the command output.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Runup delay
Locking time
Restart time
This delay ensures that during run-up between the stages, the next step can be
switched on only after the set run-up delay. This ensures that e.g. a step of the
refrigeration machine is run up before the next stage of the refrigeration machine is
switched on.
This ensures that a step that has just switched off remains off for the set period of
time. As a result, the compressor e.g. remains switched off for the set time.
Ensures that the aggregate can restart after expiration of the set time. The time
begins from the moment the aggregate is switched on. This ensures, e.g. that the
heat pump restarts only after a set time.
Switching and monitoring device RMS705B
Aggregates
C D
C
D
Range
00.00...59.59 m.s
00.00...59.59 m.s
00.00...59.59 m.s
Factory setting
00.05 m.s
00.00 m.s
00.00 m.s
99 / 216