Siemens Synco 700 RMZ785 Basic Documentation page 94

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Notes
Load assignment
Key
Load assignment
Siemens
Building Technologies
8.3.4
Binary step switch
Use the binary step switch to switch multistage aggregates. Size the aggregates
according to the binary load distribution.
 With the binary step switch, run priority changeover is not possible.
 Connect a modulating load signal to the output at aggregate A ( A).
In the binary step switch, digital outputs and number of load steps are assigned as
per the tables below to the entire switching capacity of the aggregate.
If configured without modulating output:
Configured
outputs
Cmd
A
0
+2
A = 1/3
0
+3
A = 1/7
0
+4
A = 1/15
If configured with a modulating output:
Configured
outputs
Load
A
1
+2
A = 1/4
1
+3
A = 1/8
0
= No modulating output.
1
= 1 modulating output.
Load assignment applies the following pattern:
+
0 %
100 %
+
0 %
100 %
Switching and monitoring device RMS705B
Aggregates
Load assignment
Cmd
B
Cmd
C
B = 2/3
B = 2/7
C = 4/7
B = 2/15
C = 4/15
Load assignment
Cmd
B
Cmd
C
B = 1/4
C = 2/4
B = 1/8
C = 2/8
Number of
load steps
Cmd
D
3
7
D = 8/15
15
Number of
load steps
Cmd
D
4
D = 4/8
8