Siemens Synco 700 RMZ785 Basic Documentation page 128

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Example
A-Average-, B-Max
calculation
Siemens
Building Technologies
Split function "Inputs split" is enabled.
N.X1
N.X2
N.X3
° C
° C
%
X
X
X
A
N.Y1
Function range A:
"Min-Max-Average" block calculates the average from terminal values N.X1, N.X2
(both in °C). The result is used as internal, analog signal (a) from controller 1 as
main control variable.
Function range B:
"Min-Max-Average" block calculates the maximum from terminal values N.X3, N.X4
(both in %). The result (as % value) is used as internal, analog signal (a) from
controller 1 as "Universal shift".
Switching and monitoring device RMS705B
Signal converter
N.X4
%
129 / 216
CE1P3124en