Setting values
Siemens
Building Technologies
11.3.3 Setting values for universal shift
Main menu > Commissioning > Settings > ...or
Main menu > Settings > Controller 1...3 > Setpoint effects >
Operating line
[Setp compensation 2] delta
[Setp compensation 2] end
[Setp compensation 2] start
[Setp compensation 1] start
[Setp compensation 1] end
[Setp compensation 1] delta
* Depends on analog value; here, e.g. temperature °C.
11.3.4 Troubleshooting
A check is made to see if a sensor is connected to the input when exiting the
commissioning menu.
If the sensor is connected but missing later, a fault message "[...] Sensor error
X.." is generated.
If there is no limitation sensor, limitation is disabled.
Switching and monitoring device RMS705B
Universal controller
Range
Factory setting *
0.0 K
30.0 °C
20.0 °C
0.0 °C
0.0 °C
0.0 K