Purpose
Features
Configuration
Note
60 / 216
Siemens
Building Technologies
7
7-day time switch
7.1
Time switch
On / Off
Six 7-day time switches with 6 switch-on or switch-off times are available for each
day.
Each time switch has operating line setting "Holiday priority".
If set to "Yes", the following occurs:
The time switch is set to "Off" for the defined holidays.
Defined special days are activated.
The "Holiday priority" setting is ignored if the time switch is set to "Slave".
The output of the time switch can either be processed RMS-internal or output
directly via a relay output.
You can override the time switch output via operating switch
the topmost user level.
Activate the time switches via operating line "Time switch".
Main menu > Commissioning > Extra configuration > Time switch > Time switch 1...6 >
Operating line
Time switch
Holiday priority
[Time switch 1] relay...
[Time switch 6] relay
[Time switch 1] op selector....
[Time switch 6] op selector
7.1.1
Communication
The 7-day time switches of the RMS705B can run autonomously.
7-day time switch programs of the RMS705B can be received by other RMx
controllers if RMS705B is connected to other controllers via bus. In that case,
configure RMS705B as slave.
Summary:
Autonomous 7-day time switch.
7-day time switch from bus: 7-day time switch slave (receives time switch from
bus).
The status of 7-day time switches can be received only, but not sent to the bus.
Switching and monitoring device RMS705B
7-day time switch
Range
Off, On
Yes, No
---, N.Q1, N.Q2, ...
Yes, No
. It is visible on
Factory setting
Off
No
---
No
CE1P3124en
01.04.2010