Note
Configuration
Notes
Setting values
Siemens
Building Technologies
8.1.1
Activate the logic
Activate the logic by configuring at least 1 input or the operation selector.
Use menu "Extra configuration" to configure logic functions for Logic A, B, and C.
The "Operation selector" setting in the operating line selects if the operation
selector is to be displayed in the main menu at the user level.
The operation selector allows users manual manipulations. No warning is
displayed during manual manipulations.
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Operating line
Adjustable values
[Logic A] input 1
---, X1, X2, ...
[Logic A] input 2
---, X1, X2, ...
[Logic A] input 3
---, X1, X2, ...
[Logic B] input 1
---, X1, X2, ...
[Logic B] input 2
---, X1, X2, ...
[Logic A] function
AND, NAND, OR, NOR
[Logic B] function
AND, NAND, OR, NOR
[Logic C] function
AND, NAND, OR, NOR, EXOR, EXNOR
Logic relay
---, N.Q1, N.Q2, .../ (free outputs only)
Operation selector
Yes, No
Time format
h:m, m:s
 You can select format "Hours:Minutes" as an extended time format (> 59.59 m.s)
for the logic function.
Important: The changeover impacts all time-related parameters of the logic
function block (switch-on/off delay and min. switch-on/off time).
 Time format "h:m" offers a 10-minute increment setting range.
8.1.2
Assign texts
You can assign a specific text to each logic and operation selector. The text is
displayed on the menu and in the operating line.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Logic 1...10 >
Operating line
Logic 1...10
Operation selector 1...10
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
Switching and monitoring device RMS705B
Aggregates
Range
Factory setting
Max. 20 characters
Logic 1...10
Max. 20 characters
Operation selector 1...10
Factory setting
---
---
---
---
---
OR
NOR
AND
---
No
m:s
69 / 216
CE1P3124en
01.04.2010