Makeup and mode of operation of the
controller
PID control controls the main controlled variable according to the defined setpoint.
The controller can contain max 2 sequences in the following combinations:
 One sequence: Sequence 1 or Sequence 4.
 Two sequences: Sequence 1 and 4.
Seq. 1
Setpoint
low
The "Setpoint low" (heating setpoint) is assigned to sequence 1.
Its output signal acts reverse to the load (inputs variable).
Example for heating: Outside temperature  , sequence 1 .
The "Setpoint high" (cooling setpoint) is assigned to sequence 4.
Its output signal acts reverse to the load (input variable).
Example for cooling: Outside temperature  , sequence 4 .
Functions "Heat demand" (see Section 10) and "Refrigeration demand" (see
Section 10.2) process the controller's output signal. The settings are described in
the corresponding chapters.
Switching and monitoring device RMS705B
Universal controller
Seq. 4