Siemens
Building Technologies
8.2.5
Minimum on time
For the comparator output, a minimum on-time can be set, i.e., when a switch-on
command is issued, the output remains active at least for the set min. switch-on
time.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Operating line
On time minimum
* See Notes on the time format in Section 8.2.1
The "On time minimum" always takes effect after a switch-on command.
8.2.6
Minimum off time
The minimum off time prevents aggregates from cycling too frequently.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Operating line
Off time minimum
* See Notes on the time format in Section 8.2.1
The "Off time minimum" always takes effect after a switch-off command.
8.2.7
Display values
Operation displays the output state of the comparator.
Main menu > Aggregates > Comparator 1...2 >
Operating line
State
Switching value A
Switching value B
8.2.8
Wiring test
You can directly switch on and off the comparator's relays during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Operating line
Comparator 1
Comparator 2
Switching and monitoring device RMS705B
Aggregates
Range
00.00...59.59 m.s or*
00.00...23.50 h.m
Range
00.00...59.59 m.s or*
00.00...23.50 h.m
Comment
Display of present state: Off, On.
Comment
Off, On
Off, On
Factory setting
00.00 m.s
Factory setting
00.00 m.s
CE1P3124en