Siemens Synco 700 RMZ785 Basic Documentation page 168

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Fault messages
Notes
Setting values
Setting values
Siemens
Building Technologies
11.2.2 Troubleshooting
 If no aggregates are configured for the control sequences, the "Current setpoint"
is displayed as "---".
 When the commissioning menu is exited, a check is carried out to see if the
main controlled variable exists.
 If the main controlled variable or differential input is missing, the corresponding
universal controller is switched off and a fault message is triggered (see "Fault
messages").
No.
Text
3011
[Main contr var 1] sensor error
3012
[Main contr var 2] sensor error
3013
[Main contr var 3] sensor error
11.2.3 Control parameters (P-band, integral action time,
derivative action time)
For every sequence, a P-band (Xp), an integral action time (Tn), and a derivative
action time (Tv) can be set.
 Integral action time Tn = 00:00 m.s: The controller has no I-part (PD).
 Derivative action time Tn = 00:00 m.s: The controller has no D-part (PI).
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Controller 1...3 > Control parameters >
Operating line
[Sequence 1
\_ ] Xp
[Sequence 1
\_ ] Tn
[Sequence 1
\_ ] Tv
[Sequence 4 _/
] Xp
[Sequence 4 _/
] Tn
[Sequence 4 _/
] Tv
11.2.4 Control timeout
You can enter a control timeout period, for example, to prevent the cooling valve
from opening immediately after the heating valve closes.
The controller does not add the integral action part during that period of time.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Controller 1...3 > Control parameters >
Operating line
Control timeout
Switching and monitoring device RMS705B
Universal controller
Effect
Urgent message; must not be
acknowledged.
Urgent message; must not be
acknowledged.
Urgent message; must not be
acknowledged.
Range
(type-dependent)
00.00...59.55 m.s
00.00...59.55 m.s
00.00...59.55 m.s
00.00...59.55 m.s
Range
00.00...59.55 m.s
Factory setting
(type-dependent)
30 K
03.00 m.s
00.00 m.s
30 K
03.00 m.s
00.00 m.s
Factory setting
00.00
169 / 216
CE1P3124en
01.04.2010