Siemens Synco 700 RMZ785 Basic Documentation page 88

Switching and monitoring device incl. extension modules
Table of Contents

Advertisement

Periodic changeover
Changeover by operating
hours
Note
First in first out
Siemens
Building Technologies
Periodic changeover set to "Auto" means that weekly periodic changeover of the
lead aggregate can be activated.
Periodic changeover balances out the number of operating hours between the
individual aggregates.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Range
Changeover day
--- / Monday...Sunday
Changeover time
00:00...23:59
You can set the changeover time (weekday, time) to avoid changeover to another
lead aggregate at undesirable times (e.g. weekend).
Periodic changeover set to "Auto" means that changeover by operating hours can
be activated. In this case, changeover of the lead aggregate occurs in dependence
of the lead aggregate's operating hours.
Changeover by operating hours balances out the number of operating hours
between the individual aggregates.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Range
Changeover
----, 1...1440 h
interval
There is no changeover by operating hours if "Changeover interval" is set to "---".
Operating hours changeover can be carried out with or without a changeover day
and time. To do this, both changeover day and time must be activated.
After a set time, the next aggregate is selected as lead aggregate upon
changeover time defined in periodic changeover.
Operating hours are counted only if:
 Modulating
aggregates are connected.
 Control of the modulating aggregate
Sequence selector set to "Auto" means that continuous changeover of the lead
aggregate can be activated.
The aggregate switched on first is switched off if several aggregates are switched
on and the load drops.
First-in first out balances out the number of operating hours between the individual
aggregates.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Rotary step switch > Rotary step switch 1...2 >
Operating line
Range
First in first out
No/Yes
With this setting, an additional aggregate can be switched even if the locking time
of the aggregate switched off most recently has not yet expired.
Switching and monitoring device RMS705B
Aggregates
Factory setting
---
04:00
Factory setting
---
> 80 %.
Factory setting
No
89 / 216
CE1P3124en
01.04.2010