12.4
External fault button
The fault block allows for connecting an external fault button.
The external fault button has the same function as fault button " " on
RMS705B. Both allow for concurrent operation.
The current alarm state can be externally indicated via the fault relay.
N.X1
N.X2
N.X3
Faults
Main menu > Commissioning > Extra configuration > Faults >
Operating line
Fault button external
12.5
Fault relay
To route fault messages, or for acoustic or visual indication on a control panel, e.g.
two outputs for the fault outputs "Fault relay 1" and "Fault relay 2" can be
configured on any two free outputs N.Qx.
Main menu > Commissioning > Extra configuration > Faults >
Operating line
Adjustable values / Comment
Fault relay 1
---, N.Q1 ... (free relays only) / assign fault relay.
Fault relay 2
---, N.Q1 ... (free relays only) / assign fault relay.
For "Fault relay 1", the following settings are possible:
Fault priority
Indication of fault
Fault internally
–
(optically)
Fault internally
–
(audibly)
Fault via bus
–
(audibly)
Inversion
Switching and monitoring device RMS705B
Faults
N.X5
N.X4
N.X6
N.X7
Adjustable values / Comment
---, N.X1, N.X2, ...
(digital only).
Priority at which the relay is to be energized.
The fault relay only indicates internal faults and
remains energized until faults are no longer present.
The fault relay only indicates internal faults and
remains energized until the fault is acknowledged.
The fault relay only indicates faults from the bus and
remains energized until the fault is acknowledged.
No: The relay is energized upon fault.
Yes: The relay is deenergized upon fault.